SECTION 01 | THE PLATFORM
CAMBRIDGEPORT.NET - PAGE 12
02 - PERFORMANCE
PERFORMANCE DATA
SELECTION-GRADE PERFORMANCE, FROM 
DELIVERED PROJECTS.
Guardian Series Products are selected to your design conditions — entering water temperature, 
airflow, static and sensible load. Curves below are drawn from delivered project selections; 
certified selections are issued per project from factory coil and fan software.
NET SENSIBLE CAPACITY VS. ENTERING WATER TEMPERATURE —
RED POINTS ARE DELIVERED DESIGN SELECTIONS
AIRFLOW VS. EXTERNAL STATIC — EC/IE5 FAN-ARRAY ENVELOPE;
FAN COUNT TUNES THE OPERATING POINT
≈1.0 SHR — sensible cooling for the data hall. 
Guardian Products are selected for sensible-heat-ratio  1.0 at data center design conditions — near-zero latent, 
with humidity handled by the facility DOAS. Capacity, airflow and approach are tuned to your EWT and 
supply-air setpoint.
Net Sensible Capacity
Airflow/ESP
Entering Air DB/WB
Leaving Air DB/WB
EWT/LWT
PARAMETER
DESIGN CONDITIONS - DELIVERED PROJECT SELECTIONS
Coils | Fluid
Flow/Coil WPD
Fans
GUARDIAN FA - 400
1,399 MBH (410 kW)
45,000 CFM
87.0/66.0°F
58.7/55.9°F
50.0/62.0°F
(2) 6-row | 35% PG
250 GPM/40.3 ftWG
(4-6) Infinitum EC | AFE
GUARDIAN FA - 600
2,131 MBH (625 kW)
94,800 CFM
95.0/70.7°F
73.1/63.9°F
66.0/84.1°F
(3) 6-row 16 FPI | 40% PG
275 GPM/25.3 ftWG
(9) Infinitum IE5 | AFE
GUARDIAN CRAH - 700
725 kW
91,000 CFM @ 1.25”
Per Project
Per Project
Per Project
(4) 6-row | CW
Per Project
(12) Infinitum IE5 | AFE
GUARDIAN CRAC - 700
725 kW
91,000 CFM @ 1.25”
Per Project
Per Project
Per Project
(4) 6-row | CW
Per Project
(12) Infinitum IE5 | AFE