AMBRIDGEPORT
RT
PAGE 7 - CRAH - GUARDIAN SERIES
GUARDIAN FA
THE HIGH END OF THE MARKET, ENGINEERED 
TO YOUR ENVELOPE.
When a hyperscale AI hall needs 725 kW per unit at a footprint, a discharge geometry and a 
controls spec nobody catalogs, this is the platform. Every Guardian FA is engineered to 
spec — coil bank, fan count, casing, controls — and still ships as one factory-piped,
run-tested package.
Capacity
Fan Array
Discharge
Leakage
150 – 725 kW+ | to 1-3 
MW/Hall in Dev
(12) Infinitum IE5 plenum | N+ 
redundant | Integral AFE
Vertical Upflow/Side | Per Project
<0.5% @-12” w.g. TSP | Validated 
in Test
Connection
Single-Point Victaulic or 
150# flanged
Airflow/ESP
Coil Bank
Casing
Controls
5,000 - 100,000 CFM
(4) 6-row CW V-Bank | Stainless 
Casing Option
Double-Wall, Insulated R7/inch
thermal break
Siemens S7-1200 PLC or Delta 
DDC | HMI | Full BAS
MODEL
Guardian FA - Published
GFA-150
GFA-200
GFA-300
GFA-425
GFA-500
GFA-600
GFA-725
C3 6R
135
156
283
354
403
506
568
C3 8R
145
168
306
384
439
549
618
C5 6R
142
164
297
372
424
533
597
C5 8R
153
177
322
403
461
577
649
AIRFLOW (CFM)
8,200 - 21,600
10,200 - 25,600
19,000 - 47,500
24,000 - 67,500
40,000 - 75,500
34,000 - 90,000
45,000 - 101,000
FANS
(2)
(2)
(4)
(6)
(8)
(9)
(9)